Emergency light & exit sign installation
Installation of emergency lights and emergency exit signs
- Emergency lights for indoor installation
- Emergency lights for outdoor installation
- Emergency exit signs
All our technicians have completed the electrician training required by law and work with proper safety equipment.
Where emergency lighting must be installed
Emergency luminaires must be installed along escape areas, where they are clearly visible from below, at least 2 metres above the floor (measured from the floor to the bottom of the luminaire). If installed lower than 2 metres, they must not obstruct the escape route.
Emergency luminaires are required in the following areas:
- Escape routes and exit areas.
- Outside the building after the exit: at least the same illuminance as just before leaving the building.
- Intersections: within 2 metres (horizontally) of the intersection.
- Turns: within 2 metres (horizontally) of the change of direction or turn.
- Changes of floor level: within 2 metres (horizontally) of the change of level.
- Stairs that form part of an escape route: every step must be lit directly.
- Working areas of firefighters and rescue staff in firefighting lifts, fire alarm call points, firefighting equipment points, evacuation preparation areas and first-aid equipment storage areas.
- Hazardous work areas, including electrical and mechanical plant rooms, control rooms, power rooms, switch rooms and areas near the control gear for normal and emergency lighting.
- Toilets: general toilets larger than 8 square metres and accessible toilets.
- Escalators and moving walkways that form part of an escape route.